REV 2 VCBA VERSION 10.xx SOFTWARE MANUAL
52
NOTES
Contact Low is the fastest Close time of the circuit breaker main
contacts.
Contact High is the slowest Close time of the circuit breaker main
contacts.
Contact Delta, also known as Contact Spread, is the maximum time
between the fastest and slowest contact time.
Resistor On Low is the fastest Close time of the circuit breaker insertion
resistor contacts.
Resistor On High is the slowest Close time of the circuit breaker
insertion resistor contacts.
Resistor On Delta is the maximum time between the fastest and the
slowest resistor contact time.
Up to 20 characters can be entered in the Comment field.
After entering all the values, click on the “OK” button. The following window will be
displayed:
6. This dialog box is used to define the Contact and Resistor Close-Open Times or “Contact
Live Times” (in milli-seconds). Input the corresponding values for each field and click on
the “OK” button. The following window will be displayed: